The Minnow is designed for Level control only, and to be used in conjunction with floats.
Dual single phase 240 VAC up to 0.8KW (7.5A per pump) 15A 3 pin power cable.
Notes
* The standard configuration should not be used in direct sunlight.
* Maximum ambient operating temperature: 45C, higher temperatures available on request.
* Maximum relative humidity: 95%, non-condensing.
* Designed for single phase 230/250 VAC supply with neutral.
* Limited pump sizes due to fixed enclosure and switchgear sizing.
The Minnow is a fixed speed pump control system, meaning pumps will either be running at full speed or stopped.
The Minnow is designed for Level control only, and to be used in conjunction with floats. The Minnow is most commonly used to empty pits or fill tanks, and for building services or larger residential complexes. It has numerous in-built features to help protect the system when a fault occurs. The units are powered from a conventional switched outlet and supplied with either a 10Amp 3 pin plug or a 15Amp 3 pin plug. Two 10Amp 3 pin sockets are provided for connection of each pump. Low level, cut-in, cut-out and high level floats are
wired into the control panel according to the application requirements. An Auto/Off/Man switch is provided to allow the pumps to be run automatically via the level floats or disabled when turned to Off or manually start each pump. When placed in Manual the pumps will only run for 60 seconds. The buzzer will sound and the fault light will flash when a fault occurs.